What Size Boiler Do I Need?
A combi is sized for hot water, not heating. A flat or a 1 or 2 bed home with one bathroom needs 24 to 27 kW, and a 3 or 4 bed home 28 to 34 kW, which is what Vaillant, Ideal and Viessmann all advise. System and regular boilers are sized to the heating instead. BRE puts an average semi at 7.5 kW of heat on a cold day, so the smallest size most makers sell usually covers it.
Boiler size calculator
Hot water
How many showers or baths might run at the same time?
Your main shower
A standard mixer shower head runs at about 8 litres a minute (Energy Saving Trust).
Heating
Mains water flow (optional)
Turn off every other tap, then time how long the kitchen cold tap, turned fully on, takes to fill a jug or bucket.
Combi boiler sizes and what they can run
A combi heats mains water as it flows through, so its size sets how much hot water you get at once. Each kW heats about 0.4 litres a minute by 35°C, which is roughly what it takes to turn winter mains water into a hot shower. That's the rise makers quote their flow rates at, and our figures match the flow rates in their manuals to within half a litre.
| Combi size | Hot water | Runs at once | 80 litre bath |
|---|---|---|---|
| 24 kW | 9.8 L/min | One mixer shower | About 8 minutes |
| 28 kW | 11.5 L/min | One mixer shower with some to spare | About 7 minutes |
| 30 kW | 12.3 L/min | One big shower head, or two eco showers | About 7 minutes |
| 35 kW | 14.3 L/min | A big shower head with some to spare, or two eco showers | About 6 minutes |
| 40 kW | 16.4 L/min | Two mixer showers, just | About 5 minutes |
Showers: about 6 litres a minute for an eco head, 8 for a standard mixer and 12 for a big or rainfall head. Electric showers heat their own water, so they don't count.
The kW on a combi is its hot water size
The number in a combi's name is how fast it heats hot water. Its heating output is often lower, and often the same across sizes. Ideal's Logic MAX C24, C30 and C35 all heat at 24.2 kW, and Baxi's 30 and 36 both heat at 25 kW. The smallest combis heat at 18 to 24.2 kW.
That's still far more than most homes need. The government's own modelling puts the average house at about 6 kW of heat at around minus 2°C, and it notes that most combis sold are 24 kW or more. So if a combi suits your hot water, it will almost always cope with the heating.
| Combi | Hot water | Heating, max | Heating, min | Flow at 35°C rise |
|---|---|---|---|---|
| Worcester Bosch Greenstar 4000 25kW | 25 kW* | 24 kW | 3 kW | 10.2 L/min |
| Worcester Bosch Greenstar 8000+ 32kW | 32 kW* | 29.6 kW | Not given | 13.7 L/min |
| Worcester Bosch Greenstar 8000+ 36kW | 36 kW* | 33.7 kW | Not given | 15.2 L/min |
| Worcester Bosch Greenstar 8000+ 40kW | 40 kW* | 33.7 kW | Not given | 17.1 L/min |
| Vaillant ecoTEC plus 826 | 26 kW* | 19.8 kW | 2.5 kW | 10.6 L/min |
| Vaillant ecoTEC plus 832 | 32 kW* | 24.9 kW | 3.5 kW | 13 L/min |
| Vaillant ecoTEC plus 836 | 36 kW* | 29.9 kW | 3.7 kW | 14.6 L/min |
| Vaillant ecoTEC plus 840 | 40 kW* | 29.8 kW | 4.5 kW | 16.3 L/min |
| Vaillant ecoTEC pro 24 | 23.4 kW | 23 kW | 5.2 kW | 9.6 L/min |
| Vaillant ecoTEC pro 28 | 27 kW | 24 kW | 5.2 kW | 11.1 L/min |
| Ideal Logic MAX Combi2 C24 | 24.2 kW | 24.2 kW | 4.8 kW | 9.9 L/min |
| Ideal Logic MAX Combi2 C30 | 30.3 kW | 24.2 kW | 6.1 kW | 12.4 L/min |
| Ideal Logic MAX Combi2 C35 | 35.3 kW | 24.2 kW | 7.1 kW | 14.5 L/min |
| Ideal Vogue Max Combi C26 | 26 kW | 18 kW | 3.7 kW | 10.6 L/min |
| Ideal Vogue Max Combi C32 | 32 kW | 26 kW | 4.6 kW | 13.1 L/min |
| Ideal Vogue Max Combi C40 | 40 kW | 32 kW | 5.7 kW | 16.4 L/min |
| Baxi 600 and 800 Combi 2 24 | 24 kW | 20 kW | 4.8 kW | 10.2 L/min |
| Baxi 600 and 800 Combi 2 30 | 30 kW | 25 kW | 5.8 kW | 12.2 L/min |
| Baxi 600 and 800 Combi 2 36 | 36 kW | 25 kW | 7.2 kW | 15 L/min |
From each maker's installation manual or spec sheet, checked 30 October 2026. *The size in the model name: Worcester Bosch and Vaillant's ecoTEC plus manuals give hot water heat input rather than output. Flows are the makers' figures at a 35°C rise; their flow regulators may be set a little lower.
What size system or regular boiler do I need?
A system or regular boiler heats a hot water cylinder, so its size comes down to the heating. That depends on how much heat your home loses on a cold day. BRE has worked this out for typical homes of each type and age, using the government's housing survey:
| Built | Flat | Mid terrace | End terrace | Semi-detached | Detached |
|---|---|---|---|---|---|
| Before 1900 | 8.3 | 9.1 | 14.8 | 15.5 | 22.1 |
| 1900 to 1929 | 5.3 | 8.1 | 11 | 12 | 17.6 |
| 1930 to 1949 | 5.1 | 6.8 | 8.7 | 9.2 | 14.7 |
| 1950 to 1966 | 4.1 | 5.9 | 7.5 | 7.6 | 11.3 |
| 1967 to 1975 | 3.6 | 5.9 | 6.8 | 7.7 | 11.6 |
| 1976 to 1982 | 2.8 | 4.9 | 6.2 | 6.4 | 10.1 |
| 1983 to 1990 | 2.4 | 4.6 | 5.4 | 5.3 | 9.5 |
| 1991 to 1995 | 2.4 | 4.4 | 5.3 | 5.1 | 9.9 |
| 1996 to 2002 | 2.5 | 4.7 | 5.8 | 5.1 | 9.1 |
| 2003 to 2006 | 2.3 | 4.9 | 4.9 | 4.5 | 8.8 |
| 2007 or later | 2.1 | 4 | 4.5 | 4.2 | 9.9 |
| Average | 3.7 | 5.8 | 7.4 | 7.5 | 12.2 |
Heat loss in kW on a cold day (24.2°C colder outside than in). BRE calls these illustrative estimates; the average across all homes is 7.3 kW.
The smallest system boilers start at 10 to 15 kW (Worcester Bosch 12 kW, Vaillant 10 kW, Ideal 15 kW, Baxi 15 kW), which covers most of the table with room to spare for reheating the cylinder. Only older end terraces, semis and detached houses need much more. For a closer figure, work out each room with our BTU calculator and add them up.
A mains-pressure (unvented) cylinder needs a good supply: Baxi puts the minimum at 1.5 bar and 20 litres a minute. If yours is lower, a regular boiler with a tank in the loft still works.
What the boiler makers recommend
Four big makers publish size advice. Worcester Bosch and Baxi don't publish a table, though Worcester says there is "no need or benefit" in choosing a bigger output than you need.
| Maker | 1 or 2 bed | 3 or 4 bed | Bigger homes |
|---|---|---|---|
| Vaillant | 24 to 27 kW | 28 to 34 kW | Unclear on the page |
| Ideal | 24 to 27 kW | 28 to 34 kW | 32 to 40 kW |
| Viessmann | 24 to 27 kW | 28 to 34 kW | 35 to 42 kW |
| Glow-worm | 25 kW | 30 kW | 35 kW |
| Maker | 1 or 2 bed | 3 or 4 bed | Bigger homes |
|---|---|---|---|
| Vaillant | 9 to 18 kW | 18 to 26 kW | 27 to 40 kW |
| Ideal | 12 to 15 kW | 18 to 24 kW | 30 to 40 kW |
| Glow-worm | 12 to 18 kW (2 bed) | 18 to 24 kW (3 bed), 25 to 30 kW (4 bed) | 30 kW or more (5 bed) |
Ideal groups homes by radiators, so we've put its bands in the nearest column. The makers' system boiler bands are well above BRE's heat loss figures, so treat them as an upper limit and let your engineer's heat loss calculation decide.
Check your mains water before you pick a combi
A combi can't give you more hot water than your mains supplies. Baxi's example: if the mains only gives 12 litres a minute, anything above about 29 kW is wasted. Worcester Bosch makes the same point: a bigger kW won't always mean more flow.
To check yours, turn off every other tap and time the kitchen cold tap, turned fully on, filling a 4.5 litre bucket. The water regulator's yardstick is 9 litres a minute at about 1 bar, which fills that bucket in 30 seconds. The legal minimum is lower, at 0.7 bar. If the pressure drops below that for an hour, twice in 28 days, your water company owes you £50 in England (up to £250 a year) or £25 in Wales, unless it was down to essential work or drought.
Is a bigger boiler better?
No. England's building regulations guidance says heating systems should not be significantly oversized, and that a combi should be able to turn down to the home's typical heating load. Most of the year your home needs a fraction of its cold-day figure, and a boiler that can't turn down that far switches on and off instead. The government says that cycling cuts efficiency and adds wear.
Bigger combis tend to have higher minimums. The smallest combis we checked turn down to between 2.5 and 5.2 kW, and the biggest to between 3.7 and 7.2 kW. Baxi's 24 goes down to 4.8 kW and its 36 only to 7.2 kW. If you don't need the extra hot water, the smaller boiler is cheaper to buy and better at gentle heating.
Will a new combi fit in my cupboard?
Combis are 700 to 780 mm tall, but makers also ask for space above for the flue and below for the pipes. Inside a cupboard that adds up to about 1,005 to 1,150 mm of height and 400 to 450 mm of width. Most can sit a few millimetres behind a cupboard door or panel, as long as it opens or comes off for servicing.
Drawn to the same scale from the front. The dashed box is the space the maker asks for in a cupboard.
| Combi | H x W x D | Above, below | Space needed |
|---|---|---|---|
| Worcester Greenstar 4000 | 724 x 400 x 310 mm | 170 mm, 186 mm | 1,080 x 410 mm |
| Worcester Greenstar 8000+ | 780 x 440 x 365 mm | 170 mm, 200 mm | 1,150 x 450 mm |
| Vaillant ecoTEC plus | 720 x 440 x 352 mm | 165 mm, 180 mm | 1,065 x 450 mm |
| Ideal Vogue Max | 740 x 445 x 330 mm | 165 mm, 100 mm | 1,005 x 450 mm |
| Baxi 600 Combi 2 | 700 x 395 x 285 mm | 178 mm, 150 mm | 1,028 x 400 mm |
Rules for a new gas boiler
- By law, gas boilers must be fitted by a Gas Safe registered engineer. Ask to see their ID card.
- In England, a new gas boiler must be at least 92% efficient (ErP), with a timer and room thermostat. A new combi also needs one extra: weather compensation, load compensation, smart controls or flue gas heat recovery.
- Your engineer should work out the size from a heat loss calculation, not just copy the old boiler.
What a new boiler costs
A bigger boiler costs a little more to buy, but the type of job matters more than the size. See our boiler replacement cost guide, price your own job with the boiler cost calculator, or read combi vs system boilers if you're still deciding.
Get free boiler quotes
Tell us about your home and local Gas Safe engineers will get in touch with prices. Free, with no obligation to book.
Frequently asked questions
Do I need a 25 kW or 30 kW boiler?+
It depends on your shower. A 25 kW combi gives about 10.2 litres a minute of hot water on a cold day, which is plenty for a standard mixer shower (about 8 litres a minute). A 30 kW combi gives about 12.3, enough for a big shower head, and runs an 80 litre bath in about 7 minutes instead of 8. If your mains only gives 10 litres a minute, the 30 kW won't give you any more. The heating side is often the same: Worcester Bosch's Greenstar 4000 manual lists 24 kW of heating for both its 25 and 30 kW models.
What size boiler do I need for a 3 bed house?+
For a combi, Vaillant, Ideal and Viessmann all suggest 28 to 34 kW for a 3 or 4 bed home, though a 24 to 27 kW combi runs one mixer shower comfortably. For a system or regular boiler, it comes down to heat loss: BRE puts an average semi at 7.5 kW on a cold day, so the smallest size in most ranges (10 to 15 kW) covers it. Older and detached homes need more.
How many radiators can a 30 kW boiler run?+
Look at the heating output, not the size in the name. Many 30 kW combis heat at about 24 to 25 kW. A 600 x 1000 mm double radiator gives 1,732 watts flat out, so 24 kW would run about 13 of them on full. Ideal's own guide says 24 kW for up to 10 radiators, 28 kW for 10 to 15 and 32 kW for 15 to 20.
Does a higher kW boiler cost more to run?+
Not by itself, because a boiler only burns the gas it needs. But bigger combis often can't turn down as far. Ideal's Logic MAX C24 turns down to 4.8 kW of heat, but its C35 only to 7.1 kW. When your home needs less than that, in mild weather, the boiler switches on and off, and the government says that cuts efficiency and adds wear. Bigger boilers also cost more to buy.
What size combi boiler do I need for 2 bathrooms?+
If both showers might run at once, two mixer showers need about 16 litres a minute of hot water. That takes a 35 to 42 kW combi and at least as much flow from your mains, so a system boiler with a cylinder is usually the better choice. If only one shower runs at a time, a 28 to 34 kW combi is fine.
What size system boiler do I need?+
Size it to your home's heat loss. BRE's figures range from 3.7 kW for an average flat to 12.2 kW for an average detached house. Most makers' smallest system boilers are 10 to 15 kW, which covers most homes with room to reheat the cylinder. A mains-pressure cylinder also needs about 20 litres a minute from the mains.
How do I check my mains water flow?+
Turn off every other tap, then time how long the kitchen cold tap, turned fully on, takes to fill a 4.5 litre bucket. Thirty seconds means about 9 litres a minute, the level the water regulator uses as its yardstick. Divide 270 by the seconds it took to get litres a minute.
Sources
- BRE: dwelling design heat loss estimates
- GOV.UK: Improving boiler standards and efficiency (consultation, December 2022)
- GOV.UK: Approved Document L, Volume 1: dwellings
- GOV.UK: Boiler Plus factsheet
- Worcester Bosch: Greenstar 4000 and 8000+ installation manuals
- Vaillant: ecoTEC plus and ecoTEC pro combi data
- Ideal Heating: Logic MAX Combi2 and Vogue Max Combi manuals
- Baxi: 600 Combi 2 installation manual
- Baxi: a simple guide to matching the right boiler to the right customer
- Energy Saving Trust: At Home with Water
- Waterwise: how to save water
- legislation.gov.uk: minimum water pressure and payments (England)
- CCW: low water pressure factsheet
- Gas Safe Register
- Makers' figures checked in October 2026.
Written by Chris Kervin, Co-Founder, Less.co.uk
Last updated: